The complete printable NEC reference for the C-10 exam. Ampacity tables, box fill, conduit fill, voltage drop, dwelling unit load calcs, motor sizing — everything you need to look up fast.
NEC Cram Sheet Pro
The complete exam reference
Everything the free cheat sheet covers, plus full ampacity tables, box fill calculations, conduit fill, voltage drop formulas, a dwelling unit load calc worksheet, and motor circuit sizing.
✓ Table 310.16 — Full ampacity reference (60/75/90°C)
Table 310.16Copper Conductor Ampacity (Not More Than 3 CCC in Raceway)
AWG/kcmil
60°C (TW, UF)
75°C (THW, THWN, XHHW)
90°C (THHN, XHHW-2)
14
15A
20A
25A
12
20A
25A
30A
10
30A
35A
40A
8
40A
50A
55A
6
55A
65A
75A
4
70A
85A
95A
3
85A
100A
115A
2
95A
115A
130A
1
110A
130A
145A
1/0
125A
150A
170A
2/0
145A
175A
195A
3/0
165A
200A
225A
4/0
195A
230A
260A
250
215A
255A
290A
300
240A
285A
320A
350
260A
310A
350A
400
280A
335A
380A
500
320A
380A
430A
TRAP: 240.4(D) caps small conductors: 14 AWG → 15A, 12 AWG → 20A, 10 AWG → 30A OCPD max — regardless of table ampacity. TIP: For the exam, memorize the 75°C column. Most terminations are rated 75°C.
310.15(C)(1)Conduit Fill Derating (Adjustment Factors)
Current-Carrying Conductors
Adjustment Factor
1-3
100% (no derating)
4-6
80%
7-9
70%
10-20
50%
21-30
45%
31-40
40%
41+
35%
Adjusted ampacity = Table 310.16 value × adjustment factorTRAP: Neutrals carrying ONLY unbalanced current and equipment grounds do NOT count as current-carrying conductors.
Table 310.15(B)(1)Ambient Temperature Correction Factors (Based on 30°C)
Ambient Temp (°C)
60°C Insulation
75°C Insulation
90°C Insulation
21-25
1.08
1.05
1.04
26-30
1.00
1.00
1.00
31-35
0.91
0.94
0.96
36-40
0.82
0.88
0.91
41-45
0.71
0.82
0.87
46-50
0.58
0.75
0.82
51-55
0.41
0.67
0.76
Final ampacity = Table 310.16 value × temp correction × conduit fill adjustmentTIP: When BOTH derating and temperature correction apply, multiply them together. Use the 90°C column for derating, then cap at the 75°C termination value.
2. Box Fill Calculations — Art. 314.16
Table 314.16(B)Volume Allowance Per Conductor
AWG
Volume (in³)
14
2.00
12
2.25
10
2.50
8
3.00
6
5.00
Box Fill Counting Rules:
Each conductor entering the box = 1 volume (based on its AWG)
All internal clamps combined = 1 volume (largest conductor size)
All grounds combined = 1 volume (largest ground size)
Each yoke/strap (device) = 2 volumes (largest conductor connected to it)
Pigtails & conductors that begin AND end inside the box = 0 volumes
Total box fill = (conductors × vol) + (1 × clamp vol) + (1 × ground vol) + (devices × 2 × vol)TRAP: Equipment grounds count as ONE entry regardless of how many ground wires. Pigtails do NOT count.
3. Conduit Fill — Chapter 9, Table 1
Ch. 9, Table 1Maximum Conduit Fill Percentages
# of Conductors
Max Fill %
1 conductor
53%
2 conductors
31%
3 or more
40%
Common Conductor Areas (THHN/THWN-2):
AWG
Area (in²)
AWG
Area (in²)
14
0.0097
4
0.0824
12
0.0133
3
0.0973
10
0.0211
2
0.1158
8
0.0366
1
0.1562
6
0.0507
1/0
0.1855
Common EMT Internal Areas:
Trade Size
Total Area (in²)
40% Fill (in²)
½"
0.304
0.122
¾"
0.533
0.213
1"
0.864
0.346
1¼"
1.496
0.598
1½"
2.036
0.814
2"
3.356
1.342
Required conduit area = total conductor area ÷ fill percentage (40% for 3+)TIP: Quick method — add up all conductor areas, divide by 0.40, then pick the conduit whose total area is ≥ that result.
4. Voltage Drop Formulas
NEC 210.19(A) Note / 215.2(A) NoteVoltage Drop Calculations
NEC recommends max 3% drop for branch circuits, 5% total (feeder + branch).
Single-Phase:VD = (2 × K × I × D) ÷ CMThree-Phase:VD = (1.732 × K × I × D) ÷ CMWhere:
K = resistivity constant: 12.9 (copper) or 21.2 (aluminum)
I = load current in amps
D = one-way distance in feet
CM = circular mils of conductor
Common Circular Mil Values:
AWG
CM
AWG
CM
14
4,110
4
41,740
12
6,530
3
52,620
10
10,380
2
66,360
8
16,510
1/0
105,600
6
26,240
4/0
211,600
TIP: To find minimum conductor size, rearrange: CM = (2 × K × I × D) ÷ max VD
Worked ExampleVoltage Drop — Single Phase
Problem: 120V, 16A load, 150 ft one-way, #10 Cu. What is the voltage drop? VD = (2 × 12.9 × 16 × 150) ÷ 10,380 = 61,920 ÷ 10,380 = 5.96V%VD = 5.96 ÷ 120 = 4.97% — exceeds 3% recommendationSolution: Upsize to #8 Cu (16,510 CM): VD = 61,920 ÷ 16,510 = 3.75V (3.1%) — still over 3%. Use #6 Cu for margin.
5. Dwelling Unit Load Calculation — Standard Method
Art. 220Step-by-Step Dwelling Load Calc Worksheet
Step 1 — General Lighting (220.12)____ sq ft × 3 VA/sq ft = ____ VAStep 2 — Small Appliance Circuits (210.11(C)(1))2 circuits minimum × 1,500 VA = 3,000 VAStep 3 — Laundry Circuit (210.11(C)(2))1 circuit × 1,500 VA = 1,500 VAStep 4 — Apply Table 220.42 Demand FactorsTotal of Steps 1-3 = ____ VA First 3,000 VA at 100% = 3,000 VA Remainder ____ VA at 35% = ____ VA Subtotal A = ____ VAStep 5 — Fixed Appliances (220.53)
List all fixed appliances (dishwasher, disposal, water heater, etc.). If 4+ appliances, apply 75% demand. Total fixed appliances: ____ VA × 75% = ____ VA (Subtotal B)Step 6 — Range/Oven (Table 220.55)
Single range ≤12 kW = 8,000 VA demand. Range demand = ____ VA (Subtotal C)Step 7 — Dryer (Table 220.54)
Single dryer: use nameplate or 5,000 VA minimum, whichever is larger. Dryer = ____ VA (Subtotal D)Step 8 — HVAC (220.60)
Use the LARGER of A/C or heat — do not add both. Larger of A/C or heat = ____ VA (Subtotal E)Step 9 — Total Service LoadA + B + C + D + E = ____ VA total demand ____ VA ÷ 240V = ____ amps Select next standard service size: ____ ATRAP: NEVER add A/C and heating together. Use the LARGER load only (220.60).TRAP: Use Table 220.55 demand (8 kW) for range, NOT nameplate value.TIP: Standard residential service sizes: 100A, 150A, 200A, 400A.
Neutral SizingDwelling Neutral Load (220.61)
Neutral load = total demand MINUS:
240V-only loads (A/C, water heater, baseboard heat) — 0% neutral
Range/dryer neutral — 70% of demand
Over 200A: additional derating at 70% for portion over 200A
Range neutral = Table 220.55 demand × 0.70
6. Motor Circuit Sizing — Art. 430
430.6 / Tables 430.248-250Motor Full-Load Current (FLC) — Common Values
Single-Phase, 115V/230V:
HP
115V FLC
230V FLC
½
9.8A
4.9A
¾
13.8A
6.9A
1
16A
8A
1½
20A
10A
2
24A
12A
3
34A
17A
5
56A
28A
Three-Phase, 208V/480V (Table 430.250):
HP
208V FLC
480V FLC
1
4.6A
2.0A
3
11.0A
4.8A
5
16.7A
7.6A
10
30.8A
14.0A
25
74.8A
34.0A
50
143A
65.0A
TRAP: ALWAYS use FLC from NEC tables, NEVER use motor nameplate amps. This is the #1 motor question trap.
Motor breaker = FLC × 2.50 (round UP to next standard size if needed)Overload protection (430.32):Overload = motor nameplate FLA × 1.15 (SF ≥ 1.15) or × 1.25 (SF < 1.15)Multiple motors on one feeder (430.24):Feeder conductor = largest motor FLC × 1.25 + sum of all other motor FLCsTRAP: Overloads use NAMEPLATE amps. Everything else uses TABLE FLC. Know the difference.
7. Service Entrance — Art. 230
230.24(B)Service Drop Clearances
Location
Min. Clearance
Above finished grade (pedestrian only)
10 ft
Above residential driveways
12 ft
Above commercial/public roads
15 ft
Over 0-600V: above roads (truck traffic)
18 ft
TRAP: Residential driveway = 12 ft, NOT 10 ft. 10 ft is for sidewalks/yards only.
EGC is sized based on the overcurrent device (OCPD) rating:
OCPD Rating (Amps)
EGC — Cu
EGC — Al
15
14 AWG
12 AWG
20
12 AWG
10 AWG
30
10 AWG
8 AWG
60
10 AWG
8 AWG
100
8 AWG
6 AWG
200
6 AWG
4 AWG
300
4 AWG
2 AWG
400
3 AWG
1 AWG
9. Raceway Support Spacing
Various ArticlesMaximum Support Spacing by Raceway Type
Raceway Type
Max Support Spacing
NEC Reference
EMT (Electrical Metallic Tubing)
10 ft
358.30
RMC (Rigid Metal Conduit)
10 ft
344.30
PVC (Rigid Polyvinyl Chloride)
Varies by size (3-8 ft)
352.30
IMC (Intermediate Metal Conduit)
10 ft
342.30
MC Cable (Metal Clad)
6 ft
330.30
AC Cable (Armored)
4.5 ft
320.30
NM Cable (Romex)
4.5 ft
334.30
TIP: EMT, RMC, and IMC all share 10 ft max. MC = 6 ft. NM/AC = 4.5 ft. Secured within 3 ft of boxes.TRAP: Support spacing and securing distance from boxes are different requirements.
10. Essential Formulas — Quick Reference
Core Electrical FormulasThe Formulas You Must Know
Power Law:P = V × I | P = I² × R | P = V² ÷ ROhm's Law:V = I × R | I = V ÷ R | R = V ÷ IThree-Phase Power:P = V × I × 1.732 × PF (balanced 3φ) I = P ÷ (V × 1.732 × PF)Continuous Load Sizing:Conductor ≥ 1.25 × continuous + 1.00 × non-continuous OCPD ≥ 1.25 × continuous + 1.00 × non-continuousTransformer Sizing:I = VA ÷ V (single-phase) I = VA ÷ (V × 1.732) (three-phase)Efficiency:Output = Input × Efficiency Input = Output ÷ EfficiencyVoltage Drop (Single-Phase):VD = (2 × K × I × D) ÷ CM | K(Cu) = 12.9, K(Al) = 21.2Voltage Drop (Three-Phase):VD = (1.732 × K × I × D) ÷ CM
11. Exam Day Quick Notes
StrategyKey Numbers to Memorize
The numbers that show up on every C-10 exam:
125% — continuous load sizing (conductors AND OCPD)
80% — inverse: standard OCPD continuous rating = 80% of trip
3 VA/sq ft — dwelling general lighting load
1,500 VA — per small appliance / laundry circuit
8,000 VA — single range demand (≤12 kW)
5,000 VA — minimum dryer demand
70% — neutral demand for range
75% — demand factor for 4+ fixed appliances
6 ft — max wall receptacle spacing (no point >6 ft from outlet)
24 in — max countertop receptacle spacing
25 ohms — ground rod resistance threshold (add 2nd rod)