Full Course →
NEC Cram Sheet Pro

Every table & formula on one sheet

The complete printable NEC reference for the C-10 exam. Ampacity tables, box fill, conduit fill, voltage drop, dwelling unit load calcs, motor sizing — everything you need to look up fast.

NEC Cram Sheet Pro

The complete exam reference

Everything the free cheat sheet covers, plus full ampacity tables, box fill calculations, conduit fill, voltage drop formulas, a dwelling unit load calc worksheet, and motor circuit sizing.

Table 310.16 — Full ampacity reference (60/75/90°C)
Box fill calculations (Table 314.16)
Conduit fill tables (Chapter 9)
Voltage drop formulas + worked examples
Dwelling unit load calc — step by step
Motor circuit sizing quick reference
Service entrance sizing guide
Grounding & bonding tables
Raceway support spacing
Print-optimized layout
One-time: $9.99
Get the Cram Sheet Pro
1. Conductor Ampacity — Table 310.16
Table 310.16 Copper Conductor Ampacity (Not More Than 3 CCC in Raceway)
AWG/kcmil60°C (TW, UF)75°C (THW, THWN, XHHW)90°C (THHN, XHHW-2)
1415A20A25A
1220A25A30A
1030A35A40A
840A50A55A
655A65A75A
470A85A95A
385A100A115A
295A115A130A
1110A130A145A
1/0125A150A170A
2/0145A175A195A
3/0165A200A225A
4/0195A230A260A
250215A255A290A
300240A285A320A
350260A310A350A
400280A335A380A
500320A380A430A
TRAP: 240.4(D) caps small conductors: 14 AWG → 15A, 12 AWG → 20A, 10 AWG → 30A OCPD max — regardless of table ampacity.
TIP: For the exam, memorize the 75°C column. Most terminations are rated 75°C.
310.15(C)(1) Conduit Fill Derating (Adjustment Factors)
Current-Carrying ConductorsAdjustment Factor
1-3100% (no derating)
4-680%
7-970%
10-2050%
21-3045%
31-4040%
41+35%
Adjusted ampacity = Table 310.16 value × adjustment factor TRAP: Neutrals carrying ONLY unbalanced current and equipment grounds do NOT count as current-carrying conductors.
Table 310.15(B)(1) Ambient Temperature Correction Factors (Based on 30°C)
Ambient Temp (°C)60°C Insulation75°C Insulation90°C Insulation
21-251.081.051.04
26-301.001.001.00
31-350.910.940.96
36-400.820.880.91
41-450.710.820.87
46-500.580.750.82
51-550.410.670.76
Final ampacity = Table 310.16 value × temp correction × conduit fill adjustment TIP: When BOTH derating and temperature correction apply, multiply them together. Use the 90°C column for derating, then cap at the 75°C termination value.
2. Box Fill Calculations — Art. 314.16
Table 314.16(B) Volume Allowance Per Conductor
AWGVolume (in³)
142.00
122.25
102.50
83.00
65.00
Box Fill Counting Rules:
  • Each conductor entering the box = 1 volume (based on its AWG)
  • All internal clamps combined = 1 volume (largest conductor size)
  • All grounds combined = 1 volume (largest ground size)
  • Each yoke/strap (device) = 2 volumes (largest conductor connected to it)
  • Pigtails & conductors that begin AND end inside the box = 0 volumes
Total box fill = (conductors × vol) + (1 × clamp vol) + (1 × ground vol) + (devices × 2 × vol) TRAP: Equipment grounds count as ONE entry regardless of how many ground wires. Pigtails do NOT count.
3. Conduit Fill — Chapter 9, Table 1
Ch. 9, Table 1 Maximum Conduit Fill Percentages
# of ConductorsMax Fill %
1 conductor53%
2 conductors31%
3 or more40%
Common Conductor Areas (THHN/THWN-2):
AWGArea (in²)AWGArea (in²)
140.009740.0824
120.013330.0973
100.021120.1158
80.036610.1562
60.05071/00.1855
Common EMT Internal Areas:
Trade SizeTotal Area (in²)40% Fill (in²)
½"0.3040.122
¾"0.5330.213
1"0.8640.346
1¼"1.4960.598
1½"2.0360.814
2"3.3561.342
Required conduit area = total conductor area ÷ fill percentage (40% for 3+) TIP: Quick method — add up all conductor areas, divide by 0.40, then pick the conduit whose total area is ≥ that result.
4. Voltage Drop Formulas
NEC 210.19(A) Note / 215.2(A) Note Voltage Drop Calculations
NEC recommends max 3% drop for branch circuits, 5% total (feeder + branch).

Single-Phase: VD = (2 × K × I × D) ÷ CM Three-Phase: VD = (1.732 × K × I × D) ÷ CM Where:
  • K = resistivity constant: 12.9 (copper) or 21.2 (aluminum)
  • I = load current in amps
  • D = one-way distance in feet
  • CM = circular mils of conductor
Common Circular Mil Values:
AWGCMAWGCM
144,110441,740
126,530352,620
1010,380266,360
816,5101/0105,600
626,2404/0211,600
TIP: To find minimum conductor size, rearrange: CM = (2 × K × I × D) ÷ max VD
Worked Example Voltage Drop — Single Phase
Problem: 120V, 16A load, 150 ft one-way, #10 Cu. What is the voltage drop?
VD = (2 × 12.9 × 16 × 150) ÷ 10,380 = 61,920 ÷ 10,380 = 5.96V %VD = 5.96 ÷ 120 = 4.97% — exceeds 3% recommendation Solution: Upsize to #8 Cu (16,510 CM): VD = 61,920 ÷ 16,510 = 3.75V (3.1%) — still over 3%. Use #6 Cu for margin.
5. Dwelling Unit Load Calculation — Standard Method
Art. 220 Step-by-Step Dwelling Load Calc Worksheet
Step 1 — General Lighting (220.12) ____ sq ft × 3 VA/sq ft = ____ VA Step 2 — Small Appliance Circuits (210.11(C)(1)) 2 circuits minimum × 1,500 VA = 3,000 VA Step 3 — Laundry Circuit (210.11(C)(2)) 1 circuit × 1,500 VA = 1,500 VA Step 4 — Apply Table 220.42 Demand Factors Total of Steps 1-3 = ____ VA
First 3,000 VA at 100% = 3,000 VA
Remainder ____ VA at 35% = ____ VA
Subtotal A = ____ VA
Step 5 — Fixed Appliances (220.53)
List all fixed appliances (dishwasher, disposal, water heater, etc.). If 4+ appliances, apply 75% demand.
Total fixed appliances: ____ VA × 75% = ____ VA (Subtotal B) Step 6 — Range/Oven (Table 220.55)
Single range ≤12 kW = 8,000 VA demand.
Range demand = ____ VA (Subtotal C) Step 7 — Dryer (Table 220.54)
Single dryer: use nameplate or 5,000 VA minimum, whichever is larger.
Dryer = ____ VA (Subtotal D) Step 8 — HVAC (220.60)
Use the LARGER of A/C or heat — do not add both.
Larger of A/C or heat = ____ VA (Subtotal E) Step 9 — Total Service Load A + B + C + D + E = ____ VA total demand
____ VA ÷ 240V = ____ amps
Select next standard service size: ____ A
TRAP: NEVER add A/C and heating together. Use the LARGER load only (220.60). TRAP: Use Table 220.55 demand (8 kW) for range, NOT nameplate value. TIP: Standard residential service sizes: 100A, 150A, 200A, 400A.
Neutral Sizing Dwelling Neutral Load (220.61)
Neutral load = total demand MINUS:
  • 240V-only loads (A/C, water heater, baseboard heat) — 0% neutral
  • Range/dryer neutral — 70% of demand
  • Over 200A: additional derating at 70% for portion over 200A
Range neutral = Table 220.55 demand × 0.70
6. Motor Circuit Sizing — Art. 430
430.6 / Tables 430.248-250 Motor Full-Load Current (FLC) — Common Values
Single-Phase, 115V/230V:
HP115V FLC230V FLC
½9.8A4.9A
¾13.8A6.9A
116A8A
20A10A
224A12A
334A17A
556A28A
Three-Phase, 208V/480V (Table 430.250):
HP208V FLC480V FLC
14.6A2.0A
311.0A4.8A
516.7A7.6A
1030.8A14.0A
2574.8A34.0A
50143A65.0A
TRAP: ALWAYS use FLC from NEC tables, NEVER use motor nameplate amps. This is the #1 motor question trap.
430.22 / 430.52 Motor Circuit Component Sizing
Conductor sizing (430.22): Motor conductor ampacity ≥ FLC × 1.25 Branch-circuit OCPD (Table 430.52):
OCPD TypeMax % of FLC
Dual-element (time-delay) fuse175%
Inverse-time circuit breaker250%
Instantaneous-trip breaker800% (certain motors)
Non-time-delay fuse300%
Motor breaker = FLC × 2.50 (round UP to next standard size if needed) Overload protection (430.32): Overload = motor nameplate FLA × 1.15 (SF ≥ 1.15) or × 1.25 (SF < 1.15) Multiple motors on one feeder (430.24): Feeder conductor = largest motor FLC × 1.25 + sum of all other motor FLCs TRAP: Overloads use NAMEPLATE amps. Everything else uses TABLE FLC. Know the difference.
7. Service Entrance — Art. 230
230.24(B) Service Drop Clearances
LocationMin. Clearance
Above finished grade (pedestrian only)10 ft
Above residential driveways12 ft
Above commercial/public roads15 ft
Over 0-600V: above roads (truck traffic)18 ft
TRAP: Residential driveway = 12 ft, NOT 10 ft. 10 ft is for sidewalks/yards only.
230.42 / 230.79 Service Entrance Conductors & Disconnects
  • SE conductors sized per load calculation — minimum #8 Cu or #6 Al
  • Max 6 disconnects per service (230.71) — "six-throw rule"
  • Each disconnect must be suitable for conditions, accessible, nearest point of entry
  • Main bonding jumper required at service — only point where neutral bonds to ground
TRAP: Max 6 disconnects, not 6 circuits. A single 6-breaker panel counts as 6 disconnects.
8. Grounding & Bonding Tables — Art. 250
Table 250.66 Grounding Electrode Conductor (GEC) Sizing
GEC is sized based on the largest service-entrance conductor:
Service Conductor (Cu)GEC (Cu)GEC (Al)
2 AWG or smaller8 AWG6 AWG
1 AWG or 1/06 AWG4 AWG
2/0 or 3/04 AWG2 AWG
Over 3/0 to 350 kcmil2 AWG1/0 AWG
Over 350 to 600 kcmil1/0 AWG3/0 AWG
Over 600 to 1100 kcmil2/0 AWG4/0 AWG
TRAP: Table 250.66 uses SERVICE CONDUCTOR size. Table 250.122 uses OCPD RATING. Different inputs!
Table 250.122 Equipment Grounding Conductor (EGC) Sizing
EGC is sized based on the overcurrent device (OCPD) rating:
OCPD Rating (Amps)EGC — CuEGC — Al
1514 AWG12 AWG
2012 AWG10 AWG
3010 AWG8 AWG
6010 AWG8 AWG
1008 AWG6 AWG
2006 AWG4 AWG
3004 AWG2 AWG
4003 AWG1 AWG
9. Raceway Support Spacing
Various Articles Maximum Support Spacing by Raceway Type
Raceway TypeMax Support SpacingNEC Reference
EMT (Electrical Metallic Tubing)10 ft358.30
RMC (Rigid Metal Conduit)10 ft344.30
PVC (Rigid Polyvinyl Chloride)Varies by size (3-8 ft)352.30
IMC (Intermediate Metal Conduit)10 ft342.30
MC Cable (Metal Clad)6 ft330.30
AC Cable (Armored)4.5 ft320.30
NM Cable (Romex)4.5 ft334.30
TIP: EMT, RMC, and IMC all share 10 ft max. MC = 6 ft. NM/AC = 4.5 ft. Secured within 3 ft of boxes. TRAP: Support spacing and securing distance from boxes are different requirements.
10. Essential Formulas — Quick Reference
Core Electrical Formulas The Formulas You Must Know
Power Law: P = V × I   |   P = I² × R   |   P = V² ÷ R Ohm's Law: V = I × R   |   I = V ÷ R   |   R = V ÷ I Three-Phase Power: P = V × I × 1.732 × PF   (balanced 3φ)
I = P ÷ (V × 1.732 × PF)
Continuous Load Sizing: Conductor ≥ 1.25 × continuous + 1.00 × non-continuous
OCPD ≥ 1.25 × continuous + 1.00 × non-continuous
Transformer Sizing: I = VA ÷ V   (single-phase)
I = VA ÷ (V × 1.732)   (three-phase)
Efficiency: Output = Input × Efficiency
Input = Output ÷ Efficiency
Voltage Drop (Single-Phase): VD = (2 × K × I × D) ÷ CM   |   K(Cu) = 12.9, K(Al) = 21.2 Voltage Drop (Three-Phase): VD = (1.732 × K × I × D) ÷ CM
11. Exam Day Quick Notes
Strategy Key Numbers to Memorize
The numbers that show up on every C-10 exam:
  • 125% — continuous load sizing (conductors AND OCPD)
  • 80% — inverse: standard OCPD continuous rating = 80% of trip
  • 3 VA/sq ft — dwelling general lighting load
  • 1,500 VA — per small appliance / laundry circuit
  • 8,000 VA — single range demand (≤12 kW)
  • 5,000 VA — minimum dryer demand
  • 70% — neutral demand for range
  • 75% — demand factor for 4+ fixed appliances
  • 6 ft — max wall receptacle spacing (no point >6 ft from outlet)
  • 24 in — max countertop receptacle spacing
  • 25 ohms — ground rod resistance threshold (add 2nd rod)
  • $25,000 — contractor bond amount
  • 8,000 hours — C-10 experience requirement (4 years)
  • 70% — CSLB exam passing score
Want the full course?

CertifyPro — $95 one-time

225+ practice questions, 18 study modules, timed sim exams, AI tutor, and this cram sheet included.

Get CertifyPro